KNX/EIB Building Automation Cable by EIB & EHS
Constructiones
Installation Temperature: Supra 0ºC
Temperatus operans: -15ºC ~ 70ºC
Radius tendentes minimum: VIII x diametri altiore
Signa Reference
BS EN 50090
BS EN 60228
BS EN 50290
RoHS Ordinationes
IEC60332-1
Cable Construction
Pars No. | APYE00819 pro PVC | APYE00820 pro PVC |
APYE00905 pro LSZH | APYE00906 pro LSZH | |
Structure | 1x2x20AWG | 2x2x20AWG |
Conductor Material | Solidum Oxygen Free Aeris | |
Conductor Size | 0.80mm | |
Insulation | S-PE | |
Lepidium sativum | Rubrum, nigrum | Rubrum, nigrum, flavum, album |
Cabling | Cores Retorta in Patr | Retorta metretas in bina, bina exposita |
Screen | Aluminium/Polyester Foil | |
Exhaurire filum | Tinned aeris filum | |
Vagina | PVC, LSZH | |
Vagina Coloris | Viridis | |
Cable Diameter | 5.10mm | 5.80mm |
Electrica euismod
Opus intentione | 150V |
Test Voltage | 4KV |
Conductor DCR | 37.0 Ω/km (Max. @ 20°C) |
Nulla Resistentia | 100 MΩhms/km (Min.) |
Mutua capacitas | 100 nF/Km (Max. @ 800Hz) |
inaequalis Capacitance | 200 pF/100m (Max.) |
Velocitas Propagationis | 66% |
Mechanica Characteres
Test Object | Vagina | |
Test Material | PVC | |
ante Seneca | Distrahens fortitudo (Mpa) | ≥10 |
Prolongatio (%) | ≥100 | |
Seneca Condition (℃Xhrs) | 80x168 | |
Post Seneca | Distrahens fortitudo (Mpa) | ≥80% unaged |
Prolongatio (%) | ≥80% unaged | |
Frigus Flecte (-15℃X4hrs) | Nulla vox | |
Impact Test (-15℃) | Nulla vox | |
DECREMENTUM longitudinale (%) | ≤5 |
Vexillum apertum est KNX (refer ad EN 50090, ISO/IEC 14543-3, ANSI/ASHRAE 135) aedificii commercii et domestici. Cogitationes KNX procurare possunt illuminationem, excaecationem et adaperta, HVAC, systemata securitatis, administrationem industriae, audio video, bona alba, ostentationes, remotam potestatem, etc. KNX e tribus prioribus signis evoluta; the European Systems Home Protocol (EHS), BatiBUS, and the Installation Bus (EIB).